远端模块故障现象分析及处理方法,远端 2024-04-27 22:48:43 0 0 1 故障现象 远端模块下挂的PD(比如下挂的AP、话机、摄像头等)不能正常上电。2 原理描述 远端模块作为中心交换机的PD,使用中心交换机PoE给远端模块供电。此场景下,中心交换机通过XLDP心跳报文定期将端口PoE功率发送给远端模块,远端模块根据接收的功率,减去损耗,设置对外PoE功率。未接收到心跳报文时,远端模块保持PoE功率不变。默认对外PoE功率60W。 远端模块使用电源适配器供电。此场景下,远端模块PoE供电功率为固定值。3 处理步骤步骤 1 查看远端模块设备PoE信息,供电功率是否足够。 # 执行命令行display remote-unit poe查看远端模块PoE信息,确认远端模块供电功率是否充足,电压等信息是否正常,比如,总供电为60W,电压50V左右时是正常的。 display remote-unit poe connect-interface GigabitEthernet0/0/4 ESN :21980117760123xxxxxxxx Name :- Device type :S5731-L4P2HW-RUA Connect interface :GigabitEthernet0/0/4 ------------------------------------------------------ PSE information : PoE power supply(mW) :60000 Total available power(mW) :60000 Total power consumption(mW) :0 Power peak value(mW) :0 Power voltage(V) :54 PSE reset times :0 PoE failure :NO ------------------------------------------------------步骤 2查看远端模块下行口PoE信息、端口级别、功率,供电模式是否正确。 # 执行命令行display remote-unitport poe查看远端模块端口PoE信息,确认端口供电等级、参考功率、供电模式、端口状态是否和下挂的PD匹配。 display remote-unit port poe ESN :219801177601xxxxxxxx Name :- Device type :- Connect interface :GigabitEthernet0/0/4 ------------------------------------------------------ GE1 PoE information: PD class :4 PD reference power(mW) :30000 PD current power(mW) :4200 PD peak power(mW) :4200 PD average power(mW) :4200 Power-up mode :at Force power :Disable Power ON/OFF :On Power-on delay(s) :0 Power status :Powered Current(mA) :78 Voltage(V) :53 GE2 PoE information: PD class :0 PD reference power(mW) :0 PD current power(mW) :2900 PD peak power(mW) :2900 PD average power(mW) :2900 Power-up mode :af Force power :Disable Power ON/OFF :On Power-on delay(s) :0 Power status :Powered Current(mA) :53 Voltage(V) :54 ... ...步骤 3对于远端模块作为中心交换机的PD场景,查看互联口PoE信息,级别、功率是否正确。 # 执行命令行display poe power查看中心交换机端口PoE功能状态是否正常。[HUAWEI] display poe powerCodes: REFPW(Reference power), USMPW(User set max power), CURPW(Current power), PKPW(Peak power), AVGPW(Average power) PortName Class REFPW(mW) USMPW(mW) CURPW(mW) PKPW(mW) AVGPW(mW) -------------------------------------------------------------------------------- GigabitEthernet0/0/1 - - 90000 0 0 0 GigabitEthernet0/0/2 4 30000 90000 4200 4400 4133 GigabitEthernet0/0/3 - - 90000 0 0 0 GigabitEthernet0/0/4 - - 90000 0 0 0 GigabitEthernet0/0/5 - - 90000 0 0 0 GigabitEthernet0/0/6 - - 90000 0 0 0 GigabitEthernet0/0/7 - - 90000 0 0 0 GigabitEthernet0/0/8 - - 90000 0 0 0 GigabitEthernet0/0/9 - - 90000 0 0 0 GigabitEthernet0/0/10 - - 90000 0 0 0 GigabitEthernet0/0/11 - - 90000 0 0 0 GigabitEthernet0/0/12 - - 90000 0 0 0 GigabitEthernet0/0/13 - - 90000 0 0 0 GigabitEthernet0/0/14 - - 90000 0 0 0 GigabitEthernet0/0/15 - - 90000 0 0 0 GigabitEthernet0/0/16 - - 90000 0 0 0 GigabitEthernet0/0/17 - - 90000 0 0 0 GigabitEthernet0/0/18 - - 90000 0 0 0 GigabitEthernet0/0/19 - - 90000 0 0 0 GigabitEthernet0/0/20 - - 90000 0 0 0步骤 4对于远端模块作为中心交换机的PD场景,检查XLDP PoE协商状态。# 参考远端模块上线异常,确认XLDP心跳报文是否正常。 # 对于S5732-H48XUM2CC款型,使用第一代光电复合缆连接远端模块,电口供电,光口通信,需通过命令行 poe xldp-proxy interfacemultige interface-number绑定光口与电口,光口代理电口发送PoE功率给远端模块,如果不配置该命令,远端模块默认60W对外PoE供电。 system-view [HUAWEI] interface XGigabitEthernet 0/0/1 [HUAWEI-XGigabitEthernet0/0/1] poe xldp-proxy interface MultiGE 0/0/1步骤 5非标PD,使用force power强制供电、改变供电模式等手段。 # 对于非标PD不能正常上电,可通过命令行poe force-power port number 使能端口强制供电,或通过命令行poe af-inrush enable port number 配置端口供电方式。然后通过步骤2、3查询远端模块端口供电是否正常。 [HUAWEI]remote-unit 3 [HUAWEI-remote-unit-3] poe force-power port 1 [HUAWEI-remote-unit-3] poe af-inrush enable port 2 [HUAWEI-remote-unit-3] commit [HUAWEI-remote-unit-3] quit 步骤 6请收集日志信息和配置信息,并联系技术支持人员。设备诊断信息可以通过displaydiagnostic-information命令收集。 原文标题:小行星远端模块下挂PD PoE供电异常如何处理? 文章出处:【微信公众号:华为产品资料】欢迎添加关注!文章转载请注明出处。审核编辑:汤梓红 收藏(0)